Agricultural electrical systems have their own special requirements to reduce the risk of fires, injuries, and to ensure that electric motors and other equipment operate properly.
Some of the special requirements needed for an agricultural setting include increased height of overhead lines to accommodate tall farm equipment such as combines and grain augers, special insulated wire to withstand damp environments inside farm buildings, and ground-fault circuit interrupters (GFCI) to ensure operator safety in the event of an extension cord or tool coming in contact with water.
OVERHEAD LINES
It should also be noted that there are several grain augers manufactured that can be raised and lowered by a tractor:s hydraulic unit, reducing the time and effort required to :crank: an auger up or down by hand.
Placement of Overhead Lines There are two sets of guidelines to consult for placement of overhead power lines for grain-handling systems, the National Electrical Safety Code (NESC) and the National Electric Code (NEC). NESC standards apply primarily to electrical supply equipment wires ahead of the transformer location that serves the farm. NEC standards address electrical wiring from the meter to the load site.
NESC standards for portable systems (moveable augers) requires that the height of the overhead line must be at least 18 feet above the highest port of the grain bin. This line height must be maintained on the loading side of the bin for an additional 18 feet plus the height of a bin. For example, the overhead line for a 20-foot tall bin must be at least 38 feet above the ground, and the post on the loading side must be a minimum of 38 feet from the bin:
Outside this 38-foot horizontal offset, the line may be sloped down to its regular height at a 1:1.5 ration (67 percent slope).
Figure 1
NESC standards for fixed grain-handling systems require that the overhead line serving the transformer must be a minimum of 12.5 feet above the roof of any solid structure that is not easily accessible to people. In situations where the roof of a structure is easily accessible, such as a grain bin, the height must be 18 feet above the highest port of the bin. A 7.5-foot horizontal clearance must be maintained for the height of the overhead line.
NESC also requires that any overhead lines over a roadway or path where cultivation equipment travels must be a minimum of 18.5 feet above the ground. This ensures that equipment such as a combine or tractor will not come into contact with the line. Tillage or harvesting equipment that contacts an overhead line can be as hazardous as touching the line with a grain auger.
NEC
standards, which apply to electrical lines from the meter
to the distribution points, require an 8-foot minimum clearance
above rooflines that are easily accessible to people (grain
bin roofs). NEC standards also require a 3-foot horizontal
clearance between equipment and insulated conductors and an
18-foot clearance above roadways for the transportation of
forest, orchard, grazing or cultivation equipment.
WIRING AGRICULTURAL
FACILITIES
There
are numerous variables for the electrification of barns and
other farm facilities that cannot be addressed in any single
publication. This section will provide recommendations as to
the type of wire and conduit to be used. For additional information
contact your local electrical inspector, electrician or electrical
supplier.
Non-metallic Sheathed Cable Because agricultural structures, particularly animal facilities, are frequently damp due to inadequate environmental controls, "Type NMC" or "UF" cable is recommended for most situations. These types of cables, because there is no paper installation, are able to withstand damp environments without becoming corroded.
The gauge of the cable needed for a specific circuit branch varies with the length of run and the demand of the power equipment to be connected. Table 1 is presented to give general guidelines only, check with a qualified electrician before purchasing cable to connect a branch circuit.
Table 1. Current Capacity of Certain Cables* | |||
Cable type | Conductor size (AWG No.) | Maximum Allowable Amps (Fuse size) | |
---|---|---|---|
(copper) | (aluminum) | ||
NMC, UF | #14 | #12 | 15 |
#12 | #10 | 20 | |
#10 | #8 | 30 | |
* - There are many exceptions to this table; therefore, check with a qualified electrician before purchasing cable for a branch circuit. |
Protecting Electric Cable Encasing electric cable inside conduit provides extra protection from livestock and gnawing rodents.
There are two basic types of conduit, metal and PVC (plastic). PVC is preferred inside agricultural structures because it is not corroded by moisture and is generally less expensive than metal conduit. Both metal and PVC conduit can be sealed where it joins receptacles, junction boxes, etc., reducing moisture concerns.
All
electric cable in an agricultural structure, whether it be
encased in conduit or not, should be placed in open areas
for frequent inspection and maintenance. Where possible, keep
electrical switches, wires, etc., out or the reach of livestock.
GROUND-FAULT CIRCUIT
INTERRUPTERS (GFCI)
A
ground-fault circuit interrupter (GFCI) is a circuit breaker
designed to prevent serious shock to people or animals under
certain conditions. It can reduce the risk of shock when using
electrical tools or appliances in damp or wet areas.
The GFCI works on the principle that the two wires supplying a single-phase electrical load must carry the same number of amperes (current) when the circuit is operating properly. If a ground-fault occurs, either to the grounding wire or through a person or animal, some of the current will take an alternate route back to the system:s grounding electrode. One of the wires will then carry less current than the other wire. When this occurs the GFCI will break the circuit, stopping the flow of electricity in a fraction of a second to reduce the electric shock hazard.
Ground-fault circuit interrupters come in several styles. They are commonly used as a receptacle outlet, part of an extension cord, or can be installed in the main electrical panel to replace an existing circuit breaker. When installed as a circuit breaker, the GFCI offers shock protection to an entire electrical branch.
Ground-fault circuit interrupters are available for 120-V circuits with one hot wire and a neutral. A GFCI will work on older two-wire electrical systems that have no ground wire. A 120-V, single-pole GFCI fits into the same size space as a standard single-pole breaker. There are also GFCIs for 240-V circuits using two hot wires.
All equipment plugged into a GFCI protected receptacle, including any two-prong (two-wire) electrical plug, will have ground-fault protection.
A portable GFCI is recommended for persons using power tools in damp or wet locations. The portable GFCI is plugged into an outlet and the power tool is plugged into the GFCI.
Certain conditions can result in "nuisance tripping" of a GFCI protected circuit or receptacle.
Nuisance tripping can be reduced by avoiding:
Installing
a GFCI to prevent electrical shock from farm equipment seems
like a good idea, but nuisance tripping may become a serious
problem. The loss of a ventilation system in certain livestock
facilities can be fatal to animals if the GFCI tripped. Stock
waterers may freeze in northern climates if the GFCI trips.
Carefully consider the effects of loss of power to an agricultural
circuit before installing GFCI protection. The most effective
shock prevention system for agricultural equipment and circuits
is a good equipment grounding conductor run with the circuit
wires and connected to all metal agricultural equipment.
EXTENSION CORDS
Damaged
or improperly used cords can result in electrical shocks or
start fires. Avoid using extension cords in farming operations.
Follow these precautions if you must use an extension cord:
Extension cords are sold in various cable sizes, with the smaller number being the larger wire size (a number 10 wire is larger than a number 14).
Table 2 presents some general guidelines for cord length of extension cords.
Table 2. Hard Service Extension Cords | |
Cord Length | Conductor AWG No. |
---|---|
Up to 35' | #14 |
36' to 75' | #12 |
76' to 100' | #10 |
#16
cord should be primarily for service cords on appliances
and equipment where the maximum load does not exceed
10 amperes or 1150 watts. #18 cord (PO-1 or SF-1) will safely carry a maximum load of 7 amperes or 800 watts. |
REFERENCES
Michigan State University, Agricultural Engineering Department.
Howard J. Doss, Extension Agricultural Safety Specialist; and William McLeod, Agricultural Engineering, Michigan State University Extension, East Lansing, Michigan 48824. 5/93. Funded by the National Institute of Occupational Safety and Health - #UO5/CC-4506052-02. This information is for educational purposes only. Reference to commercial products or trade names does not imply endorsement by the MSU Extension or bias against those not mentioned.